CONDENSATION & INDUSTRIAL UTILITIES
Welded Plate Steam Condenser Selection
Assess a welded plate steam condenser using the steam pressure and flow, condensate outlet requirement and cooling-medium conditions. Confirm non-condensable venting, condensate drainage and the complete operating range.
- Define the steam duty
- Provide steam mass flow, pressure, temperature and whether the inlet is saturated or superheated. State the required condensate outlet condition and any subcooling target. Include turndown and pressure variation, plus expected non-condensable gases or contaminants.
- Specify the cooling circuit
- Identify the cooling medium, inlet temperature, available flow and acceptable outlet temperature. Provide operating and design pressures and allowable pressure drop. Check the duty at the most demanding cooling-medium condition rather than only an annual average.
- Review venting and condensate drainage
- Assess vapour distribution, non-condensable removal, condensate drainage and backpressure with the surrounding system. Confirm orientation and connection requirements on the approved arrangement drawing. The exchanger and condensate system must be assessed together.
- Agree the verification basis
- Specify the required condensed flow, outlet condition, pressure drop and inspection documents. Confirm the cleaning method and panel access. Use measured steam or cooling-side data and an agreed heat balance for commissioning acceptance.
Send Your Process Data for Heat Exchanger Selection
Provide both fluids, flow rates, inlet and outlet temperatures, operating and design pressures, allowable pressure drop and material requirements. For a replacement, include the nameplate and arrangement drawing.
